Contact
Tel: 18037961302
Sales hot line ( 24 hours  service): 18037961302

E-Mail: firstfurnace@gmail.com

whatsapp:+8618037961302

Adress: Luoxin Industrial Park, Luoyang, Henan
  • Products
  • smelting equipment

    steel smelting furnace

    Small casting furnace

    Small steel melting furnace

    small induction melting furnac

    Mini induction furnace

    Copper melting furnace

    Copper melting electromagnetic

    scrap copper melting induction

    Electromagnetic copper melting

    Aluminum melting medium freque

    Electromagnetic melting alumin

    Aluminum induction furnace

    scrap aluminum melting inducti

    500KG electromagnetic melting

    300kg electromagnetic melting

    Steel induction furnace

    Induction furnace steelmaking

    5T Steel Melting Inductio

     3T Steel Melting In

    2T steel melting induction fur

    1T Steel Melting Inductio

     1T Steel Melting In

    0.25T steel melting induc

    0.5T steel melting induct

    Steel melting furnace

     Cast Iron Furnace

    iron melting furnace

    Electric furnace technical parameters
        Induction melting furnace can not start analysis
    Symptom: The device cannot be started. Only the DC current meter has an indication when starting. There is no indication for the DC voltage and the intermediate frequency voltmeter.
    Fault analysis and processing are as follows:
        1. The inverter trigger pulse has a missing pulse phenomenon. Check the inverter pulse with an oscilloscope (preferably on the G-K of the thyristor). If there is a missing pulse, check if the connection has poor contact or open circuit. Is there any pulse output at the front stage?
        2. Inverter thyristor breakdown. Use a multimeter to measure the resistance between A and K. In the absence of cooling water, the value of A-K should be greater than 10K, and the resistance is 0. If there are two damages during the measurement, remove one of the connected copper bars and judge whether one or two are damaged. Replace the thyristor and check the cause of the thyristor damage.
    3. Capacitor breakdown. Use the 〜 IK block of the pointer multimeter to measure the capacitance of each column to the common terminal. If there is no indication that the column is broken, remove the damaged capacitor pole.
    4. The load has a short circuit and grounding. The resistance of the coil to ground (without cooling water) can be measured with a 1000V megger (shake table), which should be greater than 1MΩ, otherwise the short-circuit point and grounding point should be excluded.
    5. The IF signal sampling loop has an open or short circuit. Use an oscilloscope to observe the waveform of each signal sampling point, or use a multimeter to measure the resistance value of each signal sampling loop to find the open or short point. Focus on the intermediate frequency feedback transformer, whether the primary side is open (caused by the snorkeling sensation).